POWER AND GROUNDING
TABLE Q
(continued).
-48 Volt DC Input Power Requirements
Parameter Requirements
Redundancy Redundancy of the battery chargers/rectifiers should be considered.
This would also provide the additional current necessary to recharge
the batteries after being fully discharged.
Electrical Noise Voice band noise from the battery plant to the system must be less
than 32dBmC.
Grounding A single point ground must be maintained.
A ground conductor must be installed from the isolated Ground
Discharge Bar* to the closest Approved Ground via the shortest
route as required by the NEC/REC. The gauge must be no smaller
than the largest conductor in the system and larger than 6 AWG.
The Ground Discharge Bar shall not be connected electrically to the
chassis of the battery plant chargers, power board, or inverter(s).
All output power shall be isolated from the input power.
Lightning Protection There must be adequate lightning protection in the battery plant to
ensure that the system will not be damaged.
As shown in Figure 21, the size of the wire required for the -48 V DC and -48 V return must be
engineered so that
the -48 V DC supplied by the battery plant to the G1 cabinets will be
maintained between -42.5 and -52.5 V DC at all times
to ensure proper operation and to
prevent hardware damage.
* Refer to
DEFINITY
Communications System Generic 1 and Generic 3—Installation and Test
, 555-230-104, for parts
and location information.
124